Bathroom & Kitchen Exhaust Fan CFM Calculator
Size a bathroom exhaust fan (8 ACH rule, 1 CFM per ft², HVI fixture method and ASHRAE 62.2 50 or 20 CFM) and a kitchen range hood (CFM per linear foot, BTU-based for gas ranges, island multiplier), with duct size and length limits, make-up air threshold and sone noise guidance.
How it works
Bath: CFM = volume × 8 ÷ 60, or 1 CFM/ft² (≤ 100 ft²), or 50 CFM per fixture (> 100 ft²), minimum 50; kitchen: 100 CFM per linear ft of wall hood (150 island) or gas BTU/h ÷ 100, minimum 100; equivalent duct length = length + 15 ft per elbow
Bathroom fans are sized to change the room air roughly eight times an hour, which for ordinary bathrooms works out to about one CFM per square foot with a 50 CFM floor set by ASHRAE 62.2 and the residential codes; larger bathrooms are sized per fixture because it is the shower and tub that make the steam. Range hoods scale with the width of the hood and the heat of the burners — gas cooking releases combustion products as well as grease and moisture, so one CFM per hundred BTU/h is the rule, and island hoods need half again more because cross-drafts pull the plume away. Both fans lose much of their rated flow to duct friction, so the duct size and length matter as much as the box, and hoods above 400 CFM trigger a make-up-air requirement so the kitchen does not depressurise the house and backdraft the furnace.
Worked example
A 10 × 8 ft bathroom with 8 ft ceilings needs 85 CFM by the 8 ACH rule (80 by the 1 CFM/ft² rule), so a fan rated about 110 CFM through 45 equivalent feet of 4–6″ duct. A 30″ wall hood over a 45,000 BTU/h gas range needs 450 CFM by the BTU rule (250 by width) — above 400, so make-up air is required.
Frequently asked questions
Should a bathroom fan run continuously?
ASHRAE 62.2 accepts 20 CFM continuous in place of 50 intermittent, and a quiet ECM fan running all day costs a few dollars a year while controlling humidity best. Add a boost switch or humidity sensor for showers.
Is a recirculating (ductless) range hood adequate?
It filters grease and some odour but removes no moisture, heat or combustion gases; codes count it as ventilation only where exhaust is impractical. Over a gas range, duct to the outdoors.
Related calculators
Standard HVAC field formulas (sensible heat equation, fan laws, ASHRAE 62.2 and blower-door conventions) at sea-level air density unless noted. Use manufacturer data, a Manual J/D/S load calculation and a licensed HVAC technician for design and commissioning decisions.