InfyCalculator
🔨

HVAC Superheat & Subcooling Calculator

Superheat and subcooling for R-410A, R-32, R-22, R-134a and R-454B systems from suction/liquid pressures and line temperatures — target superheat for fixed-orifice systems from indoor wet-bulb and outdoor dry-bulb, with charge diagnosis.

Refrigerant
Suction (low-side) pressure
Suction line temperature at the evaporator outlet / service valve
Liquid (high-side) pressure
Liquid line temperature at the condenser outlet
Metering device
Indoor return-air wet-bulb (fixed orifice)
Outdoor dry-bulb (fixed orifice)
Manufacturer target subcooling (TXV)
Loading calculator…

How it works

Superheat = suction line temp − saturation temp at suction pressure; subcooling = saturation temp at liquid pressure − liquid line temp; fixed-orifice target superheat ≈ (3 × indoor WB − 80 − outdoor DB) ÷ 2

Two temperatures tell a technician whether an air-conditioning system holds the right amount of refrigerant. Superheat is how far the vapour leaving the evaporator has warmed beyond its boiling point at that pressure — too little means liquid may reach the compressor, too much means a starved coil — and on fixed-orifice systems it is the charging target, varying with indoor humidity and outdoor temperature. Subcooling is how far the liquid leaving the condenser has cooled below its condensing temperature; on systems with a thermostatic or electronic expansion valve the valve holds superheat steady, so subcooling becomes the charge indicator, typically 8–12 °F. Saturation temperatures come from the refrigerant’s pressure-temperature chart; this tool interpolates those charts, accurate to about a degree over the service range. Airflow problems mimic charge problems, so check filters and coils first.

Worked example

R-410A with 118 psig suction and a 52 °F suction line: saturation is about 40 °F, so superheat is 12 °F. Liquid at 346 psig and 95 °F: condensing about 105 °F, subcooling 10 °F — a TXV system charged correctly.

Frequently asked questions

Where do I measure the temperatures?

Suction: on the suction line near the outdoor unit service valve (total superheat) or at the evaporator outlet (evaporator superheat). Liquid: on the liquid line at the condenser outlet. Insulate the probe from air and sun.

Why does target superheat change with the weather?

A fixed orifice cannot adjust flow, so on hot dry days the evaporator is starved (high superheat) and on humid mild days flooded; the target formula accounts for that so the charge is set for typical conditions.

Related calculators

Educational estimate. Electrical, plumbing and HVAC work must comply with the local code (NEC/CEC/IEC, IPC/UPC) and be checked by a licensed professional; safety limits (NIOSH, ACGIH, OSHA) are guidance, not a substitute for a workplace assessment.