InfyCalculator
🔨

Lighting Power Density (W/ft²) & Energy Code Calculator

Calculate lighting power density in watts per square foot and per square metre from installed fixture wattage and floor area, compare with ASHRAE 90.1 / IECC space-by-space allowances by occupancy type, and see the annual energy cost and the savings from controls.

Floor area
Number of luminaires
Input watts per luminaire (driver included)
Space type (allowance basis)
Annual operating hours
Electricity price
Controls credit / savings
Loading calculator…

How it works

LPD = total input watts ÷ floor area; allowed watts = allowance × area; annual kWh = watts × hours ÷ 1,000; controls saving = kWh × credit %

Energy codes limit how much lighting power a building may install per square foot, either as a whole-building number by building type or space-by-space with a different allowance for each room function — open offices around 0.6 W/ft², retail about 1.0, corridors 0.4, parking garages 0.15 in ASHRAE 90.1-2019 and the IECC that references it (California Title 24 is tighter still). LED efficacy has made compliance easy — a well-designed office now installs half its allowance — and the emphasis has shifted to mandatory controls: occupancy or vacancy sensors, automatic daylight dimming near windows, and time-of-day shutoff, which together cut actual lighting energy by a further third to a half. Lighting power also becomes heat that the cooling system must remove, so every lighting watt saved saves a little more in summer.

Worked example

30 fixtures at 32 W in a 1,200 ft² open office give 0.80 W/ft² — 31% over the 0.61 W/ft² allowance; the space allows 732 W, so 22 such fixtures (or 30 at 24 W). At 3,000 hours the 960 W installed uses 2,880 kWh — $403 a year — and occupancy sensors would save about $100.

Frequently asked questions

Do plug-in lamps and task lights count?

Hard-wired lighting counts; most codes exempt plug-in task lighting, but line-voltage track is counted at 30 W per linear foot or the actual load, whichever is greater, and decorative/display lighting gets a separate additional allowance.

Does exterior lighting have LPD limits?

Yes — by lighting zone and surface type (e.g. parking areas 0.04–0.13 W/ft², building facades 0.1–0.2 W/ft²) with mandatory curfew controls.

Related calculators

Lumen-method and point-source arithmetic with typical IES recommended illuminance levels and generic fixture data. Manufacturer photometric files (IES), the applicable energy code (ASHRAE 90.1 / IECC / Title 24) and a lighting designer govern real installations.