Retaining Wall Stability Calculator (Overturning, Sliding & Bearing)

Check a cantilever retaining wall for overturning, sliding and bearing pressure with Rankine active earth pressure and a surcharge — factors of safety, toe and heel pressures and eccentricity per metre of wall.

Units
Total wall height H (top of stem to underside of base)
Base width B
Toe length (front of base to the stem)
Stem thickness
Base slab thickness
Backfill unit weight γ
Backfill friction angle φ
Base friction coefficient μ
Surcharge on the backfill
Allowable soil bearing pressure
Concrete unit weight
Loading calculator…

How it works

Ka = tan²(45° − φ/2) · soil thrust Pa = ½·Ka·γ·H² at H/3 · surcharge thrust Pq = Ka·q·H at H/2 · FS overturning = ΣMresisting / ΣMoverturning (≥ 2.0) · FS sliding = μ·ΣW / (Pa + Pq) (≥ 1.5) · x̄ = (Mr − Mo)/ΣW, e = B/2 − x̄ · qmax,min = ΣW/B × (1 ± 6e/B) when e ≤ B/6, otherwise qmax = 2ΣW/(3x̄).

A cantilever retaining wall must not tip over, slide or overload the soil under its toe. The backfill pushes on a vertical plane through the heel with Rankine active pressure, and the weights of the stem, the base slab and the soil standing on the heel hold the wall in place. Overturning is checked about the toe, sliding against base friction, and bearing with the trapezoidal pressure from the eccentric resultant. Passive resistance in front of the toe and the surcharge on the heel are ignored, which is conservative; the safety factors (2.0 overturning, 1.5 sliding) are the usual values in standard foundation-engineering texts and many building codes. A keyed base or a wider heel improves sliding.

Worked example

A 4 m wall with a 2.8 m base (0.6 m toe, 0.3 m stem, 0.4 m slab) retains soil at 18 kN/m³ and φ = 30° with a 10 kPa surcharge. Ka = 0.333, so Pa = ½ × 0.333 × 18 × 4² = 48.0 kN/m and Pq = 0.333 × 10 × 4 = 13.3 kN/m, giving an overturning moment of 64.0 + 26.7 = 90.67 kN·m/m. The stem (25.92 kN/m), slab (26.88 kN/m) and 1.9 m of soil over the heel (123.12 kN/m) give ΣW = 175.92 kN/m and a resisting moment of 284.84 kN·m/m: FS overturning = 3.14 and FS sliding = 0.55 × 175.92/61.33 = 1.58. The resultant sits 0.296 m off centre, inside B/6, so the toe pressure is 102.7 kPa and the heel pressure 22.9 kPa — under the 150 kPa allowable.

Sources: FHWA — Soils and Foundations Reference Manual Vol. II, Chapter 9 (retaining structures) · Retaining wall — design for stability

Frequently asked questions

What factor of safety is required for a retaining wall?

Typical minimums are 2.0 against overturning (1.5 in some codes for granular backfill), 1.5 against sliding, and bearing pressure below the allowable value. IBC §1807.2.3 requires 1.5 for both overturning and sliding; many engineers use 2.0 for overturning.

Why is passive pressure ignored?

The soil in front of the toe can be excavated, eroded or loosened, and it takes much more movement to mobilise passive resistance than active pressure. Ignoring it is conservative; if you count it, most designers use only part of it and ignore the top 0.5–1 m.

How can I improve the sliding safety factor?

Widen the base (more soil weight on a longer heel), add a shear key under the base, use a granular sub-base with a higher friction coefficient, or include passive resistance in front of a key. Lowering the surcharge or using lighter backfill also helps.

What if the resultant falls outside the middle third?

Then the heel side of the base lifts off the soil and the pressure under the toe rises sharply. Most designs keep e ≤ B/6 for walls on soil (and e ≤ B/4 on rock), usually by lengthening the heel.

Does this include water pressure?

No — it assumes drained backfill with weep holes or a drain. A saturated backfill adds hydrostatic pressure (9.81 kN/m³ per metre of water) and can double the thrust, which is why drainage is essential behind retaining walls.