Water Demand Calculator (Population, Per-Capita Use & Design Flows)

Calculate the design water demand of a town or development — future population, average daily, maximum daily and peak hourly demand, storage volume and the matching wastewater flow with Harmon’s peaking factor.

Units
Current population
Annual growth rate
Design period
Per-capita demand
Maximum-day factor
Peak-hour factor
Return to sewer
Loading calculator…

How it works

Future population P = P₀ × (1 + r)ⁿ · average daily demand Qavg = P × per-capita demand ÷ 86,400 (L/s) · maximum day Qmd = K₁ × Qavg · peak hour Qmh = K₂ × Qavg · regulating storage ≈ 25% of the average daily volume · wastewater: Qww = return factor × Qavg, Harmon peaking factor PF = 1 + 14/(4 + √(P/1000)).

Water systems are sized for the population at the end of the design period, usually 20–30 years, projected here with geometric growth. The average daily demand comes from the per-capita consumption (dotación), which already includes commercial use and losses in most codes. Treatment plants and supply mains are designed for the maximum day, distribution networks for the peak hour, and tanks hold about a quarter of a day’s use to balance the hourly swings. The sewer side receives 70–85% of the water supplied, and Harmon’s formula from Ten States Standards gives its peak factor, which falls as the population grows. Fire flow, when required, is added to the maximum day.

Worked example

A town of 10,000 people growing 2% a year reaches 10,000 × 1.02²⁰ = 14,859 people in 20 years. At 200 L/person/day the average demand is 14,859 × 200/86,400 = 34.40 L/s, the maximum day is 1.3 × 34.396 = 44.71 L/s and the peak hour 2 × 34.396 = 68.79 L/s. The town uses 2,971.8 m³ a day, so regulating storage of about 743.0 m³ is needed. The sewer receives 27.52 L/s on average, and with a Harmon peaking factor of 2.78 the peak wastewater flow is 76.56 L/s.

Sources: Recommended Standards for Water Works and Wastewater Facilities (Ten States Standards) — design flows and Harmon peaking factor · AWWA M32 — Computer Modeling of Water Distribution Systems: demand peaking factors (via EPA)

Frequently asked questions

What per-capita water demand should I use?

Use the value in your national code for the climate and town size: many Latin American standards give 120–250 L/person/day (dotación), European towns use 120–200, and US systems average about 80–100 gallons per person per day for residential use, or 150 gpcd including commercial and losses.

What is the difference between maximum day and peak hour?

The maximum day is the highest daily use of the year (hot, dry weather) and sizes sources, treatment plants and transmission mains. The peak hour is the busiest hour of that day and sizes the distribution pipes and pumps, with storage tanks covering the difference.

What is Harmon’s peaking factor?

An empirical ratio of peak to average sewage flow: PF = 1 + 14/(4 + √P), with P in thousands. It is about 3.8 for 1,000 people and falls towards 2 for large cities, because flows from many users even out.

How much storage does a water system need?

Regulating (equalising) storage is commonly 20–30% of the average daily volume. Codes add fire reserve and emergency storage on top, so total tank volume is often 30–50% of a day’s demand.