Water Pressure by Elevation & Booster Pump Calculator
Calculate the water pressure lost or gained per floor or metre of elevation (0.433 psi per foot), the residual pressure at the highest fixture after elevation, meter, backflow and friction losses, and the booster pump head needed to deliver a target pressure.
How it works
Elevation loss = height × 0.433 psi/ft; residual = supply − elevation − meter − devices − friction; boost = required − residual; head (ft) = psi × 2.31; hp ≈ gpm × head ÷ (3,960 × efficiency)
Water pressure is just the weight of a column of water: every foot of rise costs 0.433 psi (2.31 feet per psi, 9.8 kPa per metre), so a fixture four storeys above the meter starts with 18 psi less before a drop is spent on friction. The residual at the highest, most distant fixture — after the meter, backflow preventer, softener and pipe friction each take their share — must still meet that fixture's minimum, typically 15–20 psi for showers and 25 psi for flushometers. When it cannot, a booster pump adds the difference, sized in feet of head at the design flow. Conversely, the ground floor of a tall building can see well over the 80 psi code maximum and needs a pressure-reducing valve, which is why high-rises are split into pressure zones.
Worked example
A 55 psi street supply feeding a fixture 42 ft up loses 18.2 psi to elevation and 22 psi to the meter, backflow device and friction, leaving 14.8 psi — 5.2 psi short of a 20 psi shower requirement. A booster adding 5.2 psi (12 ft of head) at 25 gpm needs only about 0.14 hp; in practice a 1/2 hp pump with a pressure tank, or a lower-loss backflow assembly, solves it.
Frequently asked questions
My pressure is fine when nothing runs but drops when I open a tap — is that elevation?
No — static pressure includes elevation already. A drop under flow is friction (undersized or corroded pipe, clogged filter, partly closed valve) and is fixed by larger pipe or cleaning, not by a pump.
How much pressure do tankless heaters and irrigation need?
Many tankless heaters want 30 psi minimum at rated flow; sprinkler heads need 30–45 psi at the head. Check those first — they, not the showers, often drive booster decisions.
Related calculators
Simplified sizing using common US plumbing-code tables (IPC/UPC style) and standard heat-transfer arithmetic. Local codes, listed product data and a licensed plumber or engineer govern the final design; verify pressure, temperature and fixture requirements on site.