Daylight Factor & Window Area Calculator
Estimate the average daylight factor of a room from glazed area, visible light transmittance, sky angle, room surface area and reflectance (Lynes/BRE formula), the interior lux it gives under a standard overcast sky, the glazing needed for a target daylight factor and the daylit depth rule of thumb.
How it works
DF (%) = A_glass × T × θ × M ÷ [A_total × (1 − R²)] (Lynes/BRE), with θ the visible sky angle in degrees and A_total all room surfaces; interior lux ≈ DF × 10,000 lux overcast sky
The daylight factor is the ratio of interior illuminance to the simultaneous exterior illuminance under an overcast sky, so it describes the room rather than the weather: 2% is the usual threshold for a room that feels daylit, 5% for one where electric light is rarely needed. The BRE average-daylight-factor formula captures the physics compactly — more glass and clearer glass admit more light, a wider view of sky (less obstruction) matters proportionally, and light rooms bounce daylight deeper, which is what the (1 − R²) term rewards. The approach is used for planning-stage design and for daylight credits in BREEAM and LEED's older paths; detailed design uses climate-based simulation, but the factor remains the quickest way to see whether a proposed window is enough.
Worked example
A 6 × 5 × 2.7 m room (total surface 119 m²) with 4 m² of 70% VLT glazing, a 65° sky angle and 50% reflectance has an average daylight factor of 1.8% — poorly daylit, about 180 lux under a standard overcast sky. Reaching 2% needs 4.4 m² of glass (15% of the floor), and with a 2.2 m window head the daylight only reaches 4.4 m into the 6 m deep room.
Frequently asked questions
How do I estimate the sky angle?
From the centre of the window, measure the angle between the top of the facing obstruction and the window head line (or the horizontal if the head is above): an unobstructed window sees 90°; a typical street with buildings across gives 60–70°; a light well or close building 30° or less.
Is a higher daylight factor always better?
Above about 5% rooms overheat and glare in sunny climates; the aim is enough daylight with control. Orientation, shading and glazing g-value matter as much as the factor itself.