InfyCalculator
🔨

Mixed Air Temperature & Outside Air Fraction Calculator

Find the mixed air temperature entering a coil from return and outside air temperatures and the outside-air percentage, or back-calculate the outside air fraction from three measured temperatures, with the minimum OA damper position, freeze-stat risk, economizer check and mixed-air enthalpy.

Solve for
Return air temperature
Outside air temperature
Outside air fraction
Measured mixed air temperature
Supply airflow
Required minimum outside air (ventilation)
Loading calculator…

How it works

T_mix = T_return + %OA × (T_outside − T_return); %OA = (T_mix − T_return) ÷ (T_outside − T_return); OA load = 1.08 × CFM_OA × |T_return − T_outside|

Air-handling units blend recirculated return air with fresh outside air, and the mixed temperature is simply the flow-weighted average of the two streams — which is why the same equation, read backwards, is the standard field method for measuring how much outside air a unit is really bringing in: log the three temperatures on a cold morning when the difference is large and the fraction falls out. The number matters for ventilation compliance, for the heating and cooling load the outside air imposes, and for protecting coils: hydronic coils can freeze when the mixed air drops below about 38 °F, so controls limit the damper or add preheat. In mild weather the same damper becomes an economizer, using cool outside air for free cooling.

Worked example

With 74 °F return air and 20 °F outdoors, 25% outside air produces a 60.5 °F mixed air temperature; on a 10,000 CFM unit that is 2,500 CFM of outside air needing 146,000 BTU/h of heating. Conversely, measuring 60 °F mixed air would indicate 25.9% OA. Below 38 °F mixed air — about 67% OA on this day — a freeze-stat would trip.

Frequently asked questions

Why is the temperature method inaccurate in mild weather?

When outside and return temperatures are within ~15 °F, a 1 °F sensor error becomes a 7% error in the fraction. Measure on a cold or hot day, or use CO₂ tracer methods instead.

How do I measure a representative mixed air temperature?

Poorly mixed plenums stratify — cold air along the bottom, warm along the top. Use an averaging sensor or traverse the plenum with a probe and average many points downstream of the filters where mixing is better.

Related calculators

Standard HVAC field formulas (sensible heat equation, fan laws, ASHRAE 62.2 and blower-door conventions) at sea-level air density unless noted. Use manufacturer data, a Manual J/D/S load calculation and a licensed HVAC technician for design and commissioning decisions.