Motor Synchronous Speed & Slip Calculator
Synchronous speed of an AC induction motor from supply frequency and pole count, slip percentage from the nameplate or measured rpm, rotor frequency, speed at any load or frequency (VFD), and torque from horsepower at the actual speed.
How it works
n_sync = 120 × f ÷ poles; slip s = (n_sync − n) ÷ n_sync; rotor frequency = s × f; torque (lb·ft) = hp × 5,252 ÷ rpm; VFD speed ≈ 120 × f_out ÷ poles × (1 − s)
The rotating magnetic field in an AC motor’s stator turns at the synchronous speed, fixed by line frequency and the number of magnetic poles — 3,600, 1,800, 1,200 and 900 rpm for 2, 4, 6 and 8 poles at 60 Hz (3,000/1,500/1,000/750 at 50 Hz). An induction rotor must turn a little slower so the field can induce current in it; that difference, slip, is 1–3% at full load for standard motors and shrinks toward zero when unloaded, which is why a “1,750 rpm” nameplate belongs to a 1,800 rpm four-pole machine. Slip also tells you the rotor’s electrical frequency and lets you estimate speed at other loads. A variable-frequency drive changes the synchronous speed itself, so the motor tracks any frequency with roughly the same slip, keeping torque constant up to base frequency.
Worked example
A 20 hp four-pole motor on 60 Hz has a synchronous speed of 1,800 rpm; a 1,750 rpm nameplate means 2.78% slip and a rotor frequency of 1.67 Hz. Full-load torque is 60 lb·ft (81 N·m); on a drive at 45 Hz it would run about 1,313 rpm.
Frequently asked questions
How do I find the pole count from the nameplate?
Round the nameplate speed up to the nearest synchronous speed: 3,450–3,550 → 2 poles, 1,725–1,780 → 4, 1,140–1,180 → 6, 850–880 → 8.
Synchronous and permanent-magnet motors?
They run exactly at synchronous speed (zero slip); the slip section applies only to induction (asynchronous) machines.