Convection Heat Transfer Calculator (Q = h·A·ΔT)

Convective heat transfer rate from a surface with Newton’s law of cooling (Q = h·A·ΔT): heat flux, thermal resistance and energy, with typical h values for air, water, boiling and condensation.

Units
Convection type (h)
Custom heat-transfer coefficient h (W/m²·K or Btu/h·ft²·°F)
Surface area (m² or ft²)
Surface temperature
Fluid temperature (far from the surface)
Loading calculator…

How it works

Q = h × A × (T_s − T_∞) · heat flux q = Q ÷ A = h × ΔT · thermal resistance R = 1 ÷ (h × A) · 1 W/m²·K = 0.1761 Btu/h·ft²·°F

Convection carries heat between a surface and a moving fluid. Newton’s law of cooling lumps the complicated flow near the wall into one heat-transfer coefficient h, so the heat rate is simply h times the area times the temperature difference. The value of h is what matters: still air gives only 2–25 W/m²·K, a fan raises it ten-fold, water is a hundred times better than air, and boiling or condensation is higher still (ranges from Incropera’s Fundamentals of Heat and Mass Transfer, Table 1.1). For a precise h use a Nusselt-number correlation for your geometry and flow.

Worked example

A 2 m² surface at 80 °C in still air at 20 °C, with free-convection h = 10 W/m²·K, loses 10 × 2 × 60 = 1,200 W, a heat flux of 600 W/m². Its convective resistance is 1 ÷ (10 × 2) = 0.05 K/W, and over a day it gives off 28.80 kWh. With a fan (h = 50) the same surface would lose 6,000 W.

Sources: Incropera et al. — Fundamentals of Heat and Mass Transfer, Table 1.1 (typical h values) · Engineering ToolBox — Convective heat transfer

Frequently asked questions

What is Newton’s law of cooling?

The rate of convective heat transfer is proportional to the temperature difference between a surface and the surrounding fluid: Q = h·A·ΔT. Over time it also means an object cools exponentially toward the fluid temperature.

What is a typical convection heat-transfer coefficient?

Free convection in air 2–25 W/m²·K, forced air 25–250, free convection in water 50–1,000, forced water 100–20,000, and boiling or condensing water 2,500–100,000 W/m²·K.

How do I convert h between metric and US units?

1 W/m²·K = 0.1761 Btu/h·ft²·°F, and 1 Btu/h·ft²·°F = 5.678 W/m²·K.

Should I add radiation too?

For hot surfaces in air, yes — radiation is often as large as natural convection. Add Q = ε·σ·A·(T_s⁴ − T_surr⁴) with absolute temperatures, or a radiation coefficient of about 5–7 W/m²·K near room temperature.