LMTD Calculator (Log Mean Temperature Difference)

Calculate the log mean temperature difference (LMTD) of a counterflow or parallel-flow heat exchanger from inlet and outlet temperatures, plus effectiveness and the heat-transfer area for a given duty and U.

Units
Flow arrangement
Hot fluid inlet temperature
Hot fluid outlet temperature
Cold fluid inlet temperature
Cold fluid outlet temperature
Heat duty (kW or Btu/h, optional)
Overall heat-transfer coefficient U (W/m²·K or Btu/h·ft²·°F)
Loading calculator…

How it works

LMTD = (ΔT₁ − ΔT₂) ÷ ln(ΔT₁ ÷ ΔT₂) · counterflow: ΔT₁ = Th,in − Tc,out, ΔT₂ = Th,out − Tc,in · parallel flow: ΔT₁ = Th,in − Tc,in, ΔT₂ = Th,out − Tc,out · Q = U × A × LMTD → A = Q ÷ (U × LMTD) · ε = largest stream ΔT ÷ (Th,in − Tc,in)

The log mean temperature difference is the effective driving temperature difference along a heat exchanger, because the gap between the hot and cold fluids changes from one end to the other. Multiplied by the overall coefficient U and the area A it gives the heat duty Q. Counterflow always gives a larger LMTD than parallel flow for the same temperatures, so it needs less area and can even heat the cold fluid above the hot outlet. For shell-and-tube exchangers with several passes or crossflow, multiply the counterflow LMTD by a correction factor F (usually 0.8–1) from TEMA or textbook charts.

Worked example

Hot oil cooled from 150 °C to 90 °C heats water from 30 °C to 70 °C in counterflow. The end differences are 150 − 70 = 80 °C and 90 − 30 = 60 °C, so LMTD = (80 − 60) ÷ ln(80 ÷ 60) = 69.52 °C (the arithmetic mean would be 70 °C). For a duty of 100 kW and U = 500 W/m²·K the area is 100,000 ÷ (500 × 69.52) = 2.877 m². The same temperatures in parallel flow give LMTD = 55.81 °C and need 24.6% more area. Effectiveness is 60 ÷ 120 = 50%.

Sources: Engineering ToolBox — Log mean temperature difference · Wikipedia — Logarithmic mean temperature difference

Frequently asked questions

Why use the log mean and not the average temperature difference?

Heat flow is proportional to the local temperature difference, which decays exponentially along the exchanger. Integrating that profile gives the logarithmic mean; the arithmetic mean overestimates the driving force, especially when the end differences are very unequal.

What if ΔT₁ equals ΔT₂?

Then the formula is 0 ÷ 0, but the limit is simply that common ΔT. This happens in a balanced counterflow exchanger where both fluids have the same heat capacity rate.

Is the LMTD the same in °C and °F?

No — it is a temperature difference, so it scales by 1.8 between the two (a 69.52 °C LMTD is 125.1 °F). Use the scale that matches your U value.

When do I need the LMTD correction factor F?

For multipass shell-and-tube and crossflow exchangers. Compute the counterflow LMTD, read F from the P–R charts (TEMA, Kern, Incropera) and use Q = U·A·F·LMTD. A pure counterflow or parallel-flow exchanger has F = 1.